Relion® Protection and Control650 seriesIEC 60870-5-103 Communication ProtocolManual

Page 2

Selection of standard information numbers in controldirection...55

Page 3 - Product version: 1.1

Section 1 Introduction1.1 This manualThe communication protocol manual describes a communication protocolsupported by the IED. The manual concentrat

Page 4 - Copyright

1.3 Product documentation1.3.1 Product documentation setPlanning & purchaseEngineeringInstallingCommissioningOperationMaintenanceDecommissioning

Page 5 - Disclaimer

well as verifying settings by secondary injection. The manual describes the processof testing an IED in a substation which is not in service. The chap

Page 6 - Conformity

Documents related to REB650 Identity numberProduct Guide, configured 1MRK 505 265-BENType test certificate 1MRK 505 265-TEN Documents related to REL

Page 7

650 series manuals Identity numberCommunication protocol manual, DNP3 1MRK 511 241-UENCommunication protocol manual, IEC 61850 1MRK 511 242-UENCommuni

Page 8

• LHMI messages are shown in Courier font, for example:To save the changes in non-volatile memory, select Yes and press .• Parameter names are shown

Page 9

Table 2: Backup protection functionsIEC 61850 / Functionblock nameANSI Function description Current protectionPHPIOC 50 Instantaneous phase overcu

Page 10 - Table of contents

Table 3: Control and monitoring functionsIEC 61850 / Functionblock nameANSI Function description ControlSESRSYN 25 Synchrocheck, energizing check

Page 11 - Section 1 Introduction

IEC 61850 / Functionblock nameANSI Function description I103POSCMD IED commands with position and select for IEC60870-5-103Secondary system supe

Page 13 - Introduction

IEC 61850 / Functionblock nameANSI Function description VMMXU Phase-phase voltage measurementCMSQI Current sequence component measurementVMSQI

Page 14 - Section 1 1MRK 511 243-UEN

Table 4: Designed to communicateIEC 61850 / Function blocknameANSI Function description Station communicationIEC61850-8-1 IEC61850 communication

Page 15 - 1.4 Symbols and conventions

IEC 61850 / Functionblock nameFunction descriptionDTSBEGIN Time synchronizationDTSEND Time synchronizationTIMEZONE Time synchronizationIRIG-B Time syn

Page 16

Section 2 IEC 60870-5-103 overview2.1 IEC 60870-5-103 standardIEC 60870-5-103 is defined as a companion standard for the informative elementof prote

Page 17

standard. It should also be noticed that these sets of data are mainly defined for asingle function protection IED. 650 series IEDs in turn are multi

Page 18

module, the only hardware needed is optical fibres (glass/plastic) and an opto/electrical converter for the PC/RTU.Table 7: Max distances between IED/

Page 20

Section 3 IEC 60870-5-103 communicationengineering3.1 IEC 60870-5-103 engineering in PCM600The Application Configuration tool (ACT) and the Paramete

Page 21

The general settings for IEC 60870-5-103 communication are the following:• SlaveAddress and BaudRate: Settings for slave number and communicationspeed

Page 22

First, set the IED to be synchronized via IEC 60870-5-103 either from IEDConfiguration/Time/Synchronization/TIMESYNCHGEN:1 in PST or from thelocal HMI

Page 23 - 2.1 IEC 60870-5-103 standard

Document ID: 1MRK 511 243-UENIssued: February 2011Revision: -Product version: 1.1© Copyright 2011 ABB. All rights reserved

Page 25 - Section 2

Section 4 IEC 60870-5-103 vendor specificimplementationThe signal and setting tables specify the information types supported by the IEDswith the comm

Page 26

GUID-B8A3A04C-430D-4488-9F72-8529FAB0B17D V1 ENFigure 5: Settings for CMMXU: 1All input signals to IEC 60870-5-103 I103MEAS must be connected in appli

Page 27 - Section 3

4.1.1.3 SignalsTable 9: I103MEAS Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingIL1 REAL 0.0 Service value

Page 28 - Section 3 1MRK 511 243-UEN

The IED reports all valid measuring types depending on connected signals.Upper limit for measured currents, active/reactive-power is 2.4 times rated v

Page 29

4.1.2.3 SignalsTable 11: I103MEASUSR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingINPUT1 REAL 0.0 Servic

Page 30

Function type parameter for each block in private range. Default values are definedin private range 25 – 27. One for each instance.Information number

Page 31 - Section 4

4.1.3.4 SettingsTable 14: I103AR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type

Page 32 - Section 4 1MRK 511 243-UEN

4.1.4.3 SignalsTable 15: I103EF Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting51_EFFW BOOLEAN 0 Information numb

Page 33

The delay observed in the protocol is the time difference in between the signal thatis triggering the Disturbance Recorder and the respective configur

Page 34 - I103MEASUSR

CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imp

Page 35

Name Type Default Description73_SCL REAL 0 Information number 73, fault location in ohm74_FW BOOLEAN 0 Information number 74, forward/line75_REV BOOLE

Page 36

Info. no. Message Supported TYPE GI COT64 Start phase L1 Yes 2 Y 1,7,965 Start phase L2 Yes 2 Y 1,7,966 Start phase L3 Yes 2 Y 1,7,967 Start residual

Page 37

4.1.6.2 Function blockIEC10000292-1-en.vsdI103IEDBLOCK19_LEDRS21_TESTM23_GRP124_GRP225_GRP326_GRP4IEC10000292 V1 ENFigure 11: I103IED function block4

Page 38 - I103FLTPROT

Info. no. Message Supported23 Setting group 1 active Yes24 Setting group 2 active Yes25 Setting group 3 active Yes26 Setting group 4 active Yes4.1.7

Page 39

4.1.7.4 SettingsTable 22: I103SUPERV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function t

Page 40

GUID-391D4145-B7E6-4174-B3F7-753ADDA4D06F V1 ENFigure 13: IEC 60870-5-103I103USRDEF:14.1.8.2 Function blockIEC10000294-1-en.vsdI103USRDEFBLOCK^INPUT1

Page 41

4.1.8.4 SettingsTable 24: I103USRDEF Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 5 Function t

Page 42

4.2 Commands in control direction4.2.1 Function commands for IEC 60870-5-103 I103CMD4.2.1.1 FunctionalityI103CMD is a command function block in con

Page 43

4.2.1.5 Supported information typesFunction commands in control direction, pre-defined I103CMDNumber of instances: 1Function type is selected with pa

Page 44 - I103USRDEF

4.2.2.4 SettingsTable 30: I103IEDCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 255 Function

Page 45

DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a state

Page 46

4.2.3.3 SignalsTable 31: I103USRCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandsTable 32: I103USRCMD Output signalsNam

Page 47

Function type for each function block instance in private range is selected withparameter FunctionType. Default values are defined in private range 1

Page 48

4.2.4.4 SettingsTable 36: I103GENCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 127 - 1 1 Function t

Page 49 - I103USRCMD

4.2.5.3 SignalsTable 37: I103POSCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandPOSITION INTEGER 0 Position of controll

Page 50

include the function type and the information number for each signal. Formore information on the description of the Disturbance report in the Technica

Page 51 - I103GENCMD

This section describes all data that is not exactly as specified in the standard.ASDU23In ‘list of recorded disturbances’ (ASDU23) an information elem

Page 53 - 4.3.1 Disturbance recordings

Section 5 Interoperability5.1 Physical layerTable 39: Electrical Interface SupportedEIA RS-485 Nonumber of loads No5.1.1 Optical interfaceTable 40

Page 54

5.2.2 Common address of ASDUTable 42: Common address of ASDU SupportedOne COMMON ADDRESS OF ASDU (identicalwith station address)YesMore than one COM

Page 55

5.2.3.3 Supervision indications in monitor directionTable 45: Supervision indications in monitor directionINF Semantics Supported32 Measurand supervi

Page 56

ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States rel

Page 57 - Section 5 Interoperability

INF Semantics Supported84 General start/pick-up Yes85 Breaker failure Yes86 to88Trip measuring system L1 to Trip measuringsystem L3Yes89 Trip measurin

Page 58 - Interoperability

5.2.4 Selection of standard information numbers in controldirection5.2.4.1 System functions in control directionTable 51: System functions in contro

Page 59 - Section 5

5.2.5 Basic application functionsTable 54: Basic application functionsSupported Yes Test modeNo Blocking of monitor directionYes Disturbance dataNo

Page 60

DRA#-Input ACC IEC103 meaning5 5 UL16 6 UL27 7 UL38 8 UN9 64 Private range10 65 Private range11 66 Private range12 67 Private range13 68 Private range

Page 62 - 5.2.6 Miscellaneous

Section 6 GlossaryAC Alternating currentACT Application configuration tool within PCM600A/D converter Analog-to-digital converterADBS Amplitude deadb

Page 63

CPU Central processor unitCR Carrier receiveCRC Cyclic redundancy checkCROB Control relay output blockCS Carrier sendCT Current transformerCVT Capacit

Page 64

FOX 20 Modular 20 channel telecommunication system for speech,data and protection signalsFOX 512/515 Access multiplexerFOX 6Plus Compact time-division

Page 65 - Section 6 Glossary

I-GIS Intelligent gas-insulated switchgearInstance When several occurrences of the same function are availablein the IED, they are referred to as inst

Page 66 - Glossary

apparent impedance to the fault applied to the balance point,that is, the set reach. The relay “sees” the fault but perhaps itshould not have seen it.

Page 67 - Section 6

Table of contentsSection 1 Introduction...5This manual...

Page 68

SMA connector Subminiature version A, A threaded connector with constantimpedance.SMT Signal matrix tool within PCM600SMS Station monitoring systemSNT

Page 69

dissemination of standard frequencies and time signals. UTCis derived from International Atomic Time (TAI) by theaddition of a whole number of "l

Page 72

Contact usABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00Fax +46 (0) 21 14 69 18www.abb.com/substationautomati

Page 73

Settings......31Supported information types...

Page 74 - Contact us

Signals.....................42Settings............